HAIRF Server Room Air Conditioning Unit Split Type HVAC

HAIRF Server Room Air Conditioning Unit Split Type HVAC

Product Details:

Place of Origin: CHINA
Brand Name: HAIRF
Certification: CE ROHS ISO CCC
Model Number: HADR 0652

Payment & Shipping Terms:

Minimum Order Quantity: 1 set
Price: 4999~8000USD
Packaging Details: wooden case for exporting shipping
Delivery Time: 30-35days
Payment Terms: T/T
Supply Ability: 600 unit/month
Get Best Price Contact Now

Detail Information

Name: Precision Air Conditioning Unit Used In: Computer Room
Type: Air Cooled Split Or Not: Split Type
Compressor: Scroll Expansion Valve: Heat Or Electronic
High Light:

HAIRF Server Room Air Conditioning Unit

,

Air Cooled Server Room Ac Unit

,

Crac Hvac Unit Split Type

Product Description

HAIRF Server Room Air Conditioning Unit Splite Type HVAC For IT Telecommunications Air Cooling Project

OUR MISSION

We are committed to quality products and services to meet our customer's expectations and the needs of industrials. We are dedicated to our mission and goal and we believe in long term business relationship with our customers which is based on integrity, responsiveness and quality

 

HAIRF server room air conditioning unit splite type HVAC for IT telecommunications air cooling project

 

50kw precision air heating and cooling unit 380v/3phase/50hz PAC used in server room

 

 

Model : HADR/HAUR 0201 0251 0261 0271 0301 0351 0401 1022
Cooling capaciy(1) kw 21.2 23.2 26.8 27.3 31.5 35.6 41.2 102
Air flow m³/h 6530 7050 7280 8500 9000 10000 11000 24200
EER   3.72 3.6 3.6 3.75 3.71 3.71 3.71 3.68
SHR   0.98 0.98 0.92 0.98 0.99 0.98 0.97 0.95
Compressor                  
Type   Scroll
Capacily kw 5.2 5.5 5.9 6.2 7.4 8.3 9.3 22.4
Quantity nr 1 1 1 1 1 1 1 2
I F hned coil evaporator                  
Frontal surface 0.8 0.8 0.8 1.4 1.4 1.4 1.7 2.8
Geometry mm 25X21.65
Type of fins   Hydrophilic
Fin pich mm 1.8
Fan section                  
Type   Centrigugal fan
Quantity nr 1 1 1 1 1 1 2 3
Absorbed curent A 2.5 2.5 2.8 3.2 3.5 4.1 4.4 16.5
Absorbed power W 1050 1100 1200 1300 1320 2000 2150 6300
AESP Max Speed(2) Pe 360 360 360 380 380 355 355 400
Air flter                  
Eficiency   EU4
Overall surface 5.8 5.8 5.8 6.5 6.5 6.5 7.8 13.5
Fire resistance dass                  
I Electrical heaters                  
Total heating capacity kw 5 5 5 5 5 8 8 24
Quanlily nr 2 2 2 2 2 2 2 4
Material   PTC
Humidifier                  
Capacily Kg/h 8-13 8-13 8-13 8-13 8-13 8-13 8-13 8-13
Absorbed power kw 6 6 6 6 6 6 6 6
Dimension&Weight                  
Height mm 1998 1998 1998 1998 1998 1998 1998 1998
Length mm 1000 1000 1000 1000 1000 1000 1750 2500
Depth mm 795 795 795 795 795 795 795 795
Weight kg 375 385 393 450 490 590 595 1015
Sound level                  
Sound pressure level(3) db(A) 52 53 53 55 56.5 58 60 66

 