HAIRF Module Data Center
|
Model |
HMDC-0803 |
HMDC-0805 |
HMDC-0808 |
HMDC-1603 |
HMDC-1605 |
HMDC-1608 |
HMDC-2403 |
HMDC-2405 |
HMDC-2408 |
|
Cabinet subsystem |
|||||||||
|
Dimension |
W*D*H:600*1100*2000mm,Other sizes can be customized |
||||||||
|
Quantity |
8 units |
16 units |
24 units |
||||||
|
Cabinet Power density |
3kw/rack |
3kw/rack |
8kw/rack |
3kw/rack |
5kw/rack |
8kw/rack |
3kw/rack |
5kw/rack |
8kw/rack |
|
Cabinet Total power |
24KW |
40KW |
64KW |
48KW |
80KW |
128KW |
72KW |
120KW |
192KW |
|
Cabinet power supply |
Dual PDU power supply |
||||||||
|
Distribution subsystem |
|||||||||
|
Power supply |
2N power supply,Tier I grade |
||||||||
|
Column counter |
Precision column cabinet: double loop power supply |
||||||||
|
UPS |
Modular UPS |
||||||||
|
Model |
X7-50 |
X7-75 |
X7-100 |
X7-75 |
X7-100 |
X7-150 |
X7-100 |
X7-150 |
X7-250 |
|
Capacity |
50kVA |
75kVA |
100kVA |
75kVA |
100kVA |
150kVA |
100nVA |
150kVA |
250nVA |
|
Configuration |
2 sets |
2 sets |
2 sets |
2 sets |
2 sets |
2 sets |
2 sets |
2 sets |
2 sets |
|
Redundant architecture |
2(N+1) |
2(N+1) |
2(N+1) |
2(N+1) |
2(N+1) |
2(N+1) |
2(N+1) |
2(N+1) |
2(N+2) |
|
Refrigeration subsystem |
|||||||||
|
PAC |
In-row air conditioner |
||||||||
|
Model |
R261A |
R401A |
R261A |
R161A |
R261A |
R261A |
R261A |
R261A |
R401A |
|
Air supply |
Horizontal air supply |
||||||||
|
Cooling method |
Air-cooled/water-cooed/chilled water |
||||||||
|
Cooling capacity |
25.5kW |
41.5KW |
25.5KW |
15.5KW |
25.5KW |
25.5KW |
25.5KW |
25.5KW |
41.5KW |
|
Configuration |
2 pcs |
2 pcs |
4 pcs |
4 pcs |
4 pcs |
6 pcs |
4 pcs |
6 pcs |
6 pcs |
|
Redundant architecture |
1+1 redundancy |
1+1 redundancy |
3+1 redundancy |
3+1 redundancy |
3+1 redundancy |
5+1 redundancy |
3+1 redundancy |
5+1 redundancy |
5+1 redundancy |
|
Monitoring subsystem |
|||||||||
|
Terminal interface |
21 inch human touch screen |
||||||||
|
UPS monitoring |
Support |
||||||||
|
Battery Online monitoring |
Support(optional) |
||||||||
|
Power distribution monitoring |
Support |
||||||||
|
PAC monitoring |
Support |
||||||||
|
Leakage monitoring |
Support |
||||||||
|
Temperature and humidity monitoring |
Support |
||||||||
|
Smoke monitoring |
Support,Credit card/password/fingerprint(optional) |
||||||||
|
CCTV |
Support |
||||||||
|
Access control |
Support |
||||||||
|
System status |
|||||||||
|
Size*W |
5.1*3.4m |
5.4*3.4m |
5.4*3.4m |
7.8*3.4m |
7.8*3.4m |
8.1*3.4m |
10.2*3.4m |
10.5*3.4m |
12*3.4m |
|
Area |
17.34m2 |
18.36m2 |
18.36m2 |
26.52m2 |
26.52m2 |
27.54m2 |
34.68m2 |
35.7m2 |
40.8m2 |