H-series
- Commodity name: H-series
- Commodity ID: 5
Category:
It strictly complies with CE and IEC standards and is empowered with advanced electric control technology and able to work under a power source of 380V±20%. In addition, it is installed with a power supply protection module, enabling it to make a selection of protective value in a range of 380V±50%. When voltage goes beyond the selected range, it will automatically protect the unit. While the voltage becomes normal, it will automatically restart the unit.
Product Details
High quality control component
It strictly complies with CE and IEC standards and is empowered with advanced electric control technology and able to work under a power source of 380V±20%. In addition, it is installed with a power supply protection module, enabling it to make a selection of protective value in a range of 380V±50%. When voltage goes beyond the selected range, it will automatically protect the unit. While the voltage becomes normal, it will automatically restart the unit.
Evaporator
An efficient evaporator made from quality material with advanced professional technology and featuring large heat exchange area and realization of higher sensible heat factor of precision air conditioning unit.
Expansion
Expansion valve adopts advanced thermal expansion valves with strong reliability and stability and can precisely control the supply of refrigerant. In order to achieve the reduction of energy consumption for refrigerant equipment, we employ advanced electronic expansion valves in high-performance precision air conditioning units to realize less energy consumption.
Humidifier
An internationally advanced electrode steam humidification system under which the amount of humidification and water inflow and outflow are all controlled by computer, the auto cleaning program for the humidifier cylinder ensure normal humidification efficiency of the cylinder.
Cabinet
With unique frame design and black framework demonstrating consummate production technology, professional design and elegant appearance, the cabinet guarantee the safety of unit under any transport condition and operating environment.
Filter
Air filer under G4 standard which is metallic bracket, filtering the dust and particulate effectively by air circulation, then purifying the air environment of telecom room.
Scroll Compressor
The core power of unit is from Copeland hermetic scroll compressor that guarantees the high efficiency, low noise and long life of the unit.
Indoor blower fan
A blow fan adopts direct drive centrifugal fan with backward curved blades, the range of static pressure can be adjusted from 0 to 400pa, realizing the continuous operation of 365 days*24 hours, 10 years’ average life. The high-performance unit employ energy-saving EC fan controlled by 0-10V signal,DC driven and stepiess speed regulation, which is more excellent than traditional fan in energy-saving field.
Heater
An electric heater with perfect overheat protection function and ionization resistance, able to meet environmental requirements of the small heat-load machine rooms for base stations in cold arctic-alpine area.
Condenser
With an enclosure of anti-corrosion alloy that ensures service life and appearance of the condenser, an external rotor axial flow fan that is elaborately designed and able to satisfy the environment protection requirements on noise,and a fan speed regulator that controls the rotating speed under different temperature and ensure sound operating effect and energy saving.
Model:HADR/HAUR |
0201 |
0251 |
0261 |
0271 |
0301 |
0351 |
0401 |
0451 |
|
Cooling capacity(1) |
kw |
21.2 |
23.2 |
26.8 |
27.3 |
31.5 |
35.6 |
41.2 |
44 |
Air flow |
m3/h |
6530 |
7050 |
7280 |
8500 |
9000 |
10000 |
11000 |
13000 |
EER |
|
3.72 |
3.60 |
3.60 |
3.75 |
3.71 |
3.71 |
3.71 |
3.68 |
SHR |
|
0.98 |
0.98 |
0.92 |
0.98 |
0.99 |
0.98 |
0.97 |
0.95 |
Compressor |
|||||||||
Type |
Scroll |
||||||||
Capacity |
kw |
5.2 |
5.5 |
5.9 |
6.2 |
7.4 |
8.3 |
9.3 |
10.1 |
Quantity |
nr |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
Finned coil evaporator |
|||||||||
Frontal surface |
m2 |
0.8 |
0.8 |
0.8 |
1.4 |
1.4 |
1.4 |
1.7 |
1.7 |
Geometry |
mm |
25*21.65 |
|||||||
Type of fans |
Hydrophilic |
||||||||
Fin pitch |
mm |
1.8 |
|||||||
Fan section |
|||||||||
Type |
Centrifugal fan |
||||||||
Quantity |
nr |
1 |
1 |
1 |
1 |
1 |
1 |
2 |
2 |
Absorbed current |
A |
2.5 |
2.5 |
2.8 |
3.2 |
3.5 |
4.1 |
4.4 |
4.9 |
Absorbed power |
W |
1050 |
1100 |
1200 |
1300 |
1320 |
2000 |
2150 |
2400 |
AESP Max Speed(2) |
Pa |
360 |
360 |
360 |
380 |
380 |
355 |
355 |
355 |
Air filter |
|||||||||
Efficiency |
EU4 |
||||||||
Overall surface |
m2 |
5.8 |
5.8 |
5.8 |
6.5 |
6.5 |
6.5 |
7.8 |
7.8 |
Fire resistance class |
1 |
||||||||
Electrical heaters |
|||||||||
Total heating capacity |
kw |
5 |
5 |
5 |
5 |
5 |
8 |
8 |
8 |
Quantity |
nr |
2 |
2 |
2 |
2 |
2 |
2 |
2 |
2 |
Material |
PTC |
||||||||
Humidifier |
|||||||||
Capacity |
Kg/h |
8-13 |
8-13 |
8-13 |
8-13 |
8-13 |
8-13 |
8-13 |
8-13 |
Absorbed power |
kw |
6 |
6 |
6 |
6 |
6 |
6 |
6 |
6 |
Dimension&Weight |
|||||||||
Height |
mm |
1998 |
1998 |
1998 |
1998 |
1998 |
1998 |
1998 |
1998 |
Length |
mm |
1000 |
1000 |
1000 |
1000 |
1000 |
1000 |
1750 |
1750 |
Depth |
mm |
795 |
795 |
795 |
795 |
795 |
795 |
795 |
795 |
Weight |
kg |
375 |
385 |
393 |
450 |
490 |
590 |
595 |
610 |
Sound level |
|||||||||
Sound pressure level(3) |
dB(A) |
52 |
53 |
53 |
55 |
56.5 |
58 |
60 |
60 |
Model:HADR/HAUR |
0272 |
0322 |
0362 |
0422 |
0452 |
0512 |
0522 |
0652 |
0692 |
0752 |
0852 |
0912 |
1022 |
|
Cooling capacity(1) |
kw |
26.9 |
31.9 |
35.9 |
41.9 |
44.3 |
50.5 |
54.4 |
61.4 |
68.7 |
76.2 |
85.5 |
90.8 |
102 |
Air flow |
m3/h |
8000 |
9000 |
10000 |
11500 |
12950 |
13500 |
16000 |
17500 |
18000 |
21000 |
23500 |
23500 |
24200 |
EER |
|
3.60 |
3.65 |
3.66 |
3.61 |
3.63 |
3.72 |
3.72 |
3.65 |
3.61 |
3.61 |
3.61 |
3.65 |
3.62 |
SHR |
|
0.95 |
0.96 |
0.93 |
0.95 |
0.93 |
0.93 |
0.95 |
0.96 |
0.95 |
0.93 |
0.95 |
0.94 |
0.93 |
Compressor |
||||||||||||||
Type |
Scroll |
|||||||||||||
Capacity |
kw |
6.0 |
7.0 |
8.2 |
9.2 |
10.0 |
11.0 |
11.2 |
13.6 |
15.8 |
17.6 |
18.6 |
19.6 |
22.4 |
Quantity |
nr |
2 |
2 |
2 |
2 |
2 |
2 |
2 |
2 |
2 |
2 |
2 |
2 |
2 |
Finned coil evaporator |
||||||||||||||
Frontal surface |
m2 |
1.7 |
1.7 |
1.7 |
1.7 |
1.7 |
1.7 |
1.7 |
1.7 |
1.7 |
2.8 |
2.8 |
2.8 |
2.8 |
Geometry |
mm |
25*21.65 |
||||||||||||
Type of fins |
Hydrophilic |
|||||||||||||
Fin pitch |
mm |
1.8 |
||||||||||||
Fan section |
||||||||||||||
Type |
Centrifugal fan |
|||||||||||||
Quantity |
nr |
2 |
2 |
2 |
2 |
2 |
2 |
2 |
2 |
2 |
3 |
3 |
3 |
3 |
Absorbed current |
A |
4.3 |
4.3 |
4.3 |
4.4 |
4.4 |
4.4 |
5 |
5.2 |
5.2 |
6.5 |
16.5 |
16.5 |
16.5 |
Absorbed power |
W |
1600 |
1600 |
1800 |
1800 |
2000 |
2000 |
3000 |
3300 |
3900 |
3900 |
5400 |
6300 |
6300 |
AESP Max Speed(2) |
Pa |
380 |
380 |
380 |
355 |
355 |
355 |
380 |
380 |
380 |
360 |
400 |
400 |
400 |
Air filter |
||||||||||||||
Efficiency |
EU4 |
|||||||||||||
Overall surface |
m2 |
7.8 |
7.8 |
7.8 |
7.8 |
7.8 |
7.8 |
7.8 |
7.8 |
7.8 |
13.5 |
13.5 |
13.5 |
13.5 |
Fire resistance class |
1 |
|||||||||||||
Electrical heaters |
||||||||||||||
Total heating capacity |
kw |
5 |
5 |
5 |
10 |
10 |
10 |
10 |
10 |
10 |
12 |
12 |
24 |
24 |
Quantity |
nr |
2 |
2 |
2 |
3 |
3 |
3 |
3 |
3 |
3 |
2 |
2 |
4 |
4 |
Material |
PTC |
|||||||||||||
Humidifier |
||||||||||||||
Capacity |
Kg/h |
8-13 |
8-13 |
8-13 |
8-13 |
8-13 |
8-13 |
8-13 |
8-13 |
8-13 |
8-13 |
8-13 |
8-13 |
8-13 |
Absorbed power |
kw |
6 |
6 |
6 |
6 |
6 |
6 |
6 |
6 |
6 |
6 |
6 |
6 |
6 |
Dimension&Weight |
||||||||||||||
Height |
mm |
1998 |
1998 |
1998 |
1998 |
1998 |
1998 |
1998 |
1998 |
1998 |
1998 |
1998 |
1998 |
1998 |
Length |
mm |
1750 |
1750 |
1750 |
1750 |
1750 |
1750 |
1750 |
1750 |
1750 |
2500 |
2500 |
2500 |
2500 |
Depth |
mm |
795 |
795 |
795 |
795 |
795 |
795 |
795 |
795 |
795 |
795 |
795 |
795 |
795 |
Weight |
kg |
565 |
580 |
590 |
605 |
615 |
615 |
620 |
625 |
625 |
979 |
985 |
992 |
1015 |
Sound level |
||||||||||||||
Sound pressure level(3) |
Db(A) |
56 |
58 |
59 |
62 |
62 |
63 |
64 |
65 |
65 |
65 |
65 |
65 |
66 |
Product Consulting